Flame Burner


Working Principle:

As the air and fuel is controlled at the nozzle outlet in proportional burners, adverse changes in operating conditions that entail to ineffective burning is thus eliminated. As shown in the figure below, the injection air enters the burner from the same and single connection with its entirety, whereby the balancing adjustment of the air together with the fuel is performed with a single control lever.

These are burners that are used in rolling mills, industrial furnaces and equipment, capable of working with both liquid and gas fluids, but provide high temperature, in any case. Designed for burning any kinds of heavy oil, these burners are adjusted to fine tune with the particular needs, until the maximum savings are guaranteed in terms of fuel and controlled from a single lever synchronously, once a good combustion is achieved. Once the selected burning rate is determined, it shall be arranged automatically. Burners employed on the same circuit in multiples cannot only be controlled with separate control levers but also controlled from the same control lever at the same time, when interconnected together. A V shaped groove fine tunes mechanism prevents congestions of the fuel valve. In order to get the maximum performance out of proportional burners, the air requirement is met via air fans or preferably a blower.

Burner Capasity Chart

SECOND AIR JACKET CLOSED

 
Burner NO Fittings Air Pressure
350 mms
Air Pressure
500 mms
Air Pressure
700 mms
Air Pressure
900 mms
Air Pressure 1050 mms Air Pressure 1400 mms Weight kg
Air Fuel Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h
max min max min max min max min max min max min
580A 1½” R¼” 30 4 1,06 45 6 1,6 60 8 2,12 80 10 2,5 100 11,5 2,8 120 12 3,2 4
V780 1½”

R¼”

75 7,2 1,9 92 8,7 2,3 105 10,5 2,5 117 11,6 3,1 129 12,3 3,5 148 14,4 3,8 14
V781 2”

R¼”

144 14,4 3,1 117 17,5 3,5 204 19,8 4,3 230 22 4,5 250 24 5 289 27,7 5,5 18,5
V782 2”

R¼”

240 22,3 5 293 28 5,2 340 32,5 7 380 36,7 8 415 40 8,7 474 45 9,8 18,5
V783 6” R½” 432 42,5 9,2 528 53 11,5 612 60 13 680 67 14,5 750 73 15,5 864 84 18 83,5
V784 6”

R½”

850 82 16,3 1040 100 20 1206 115 23 1340 130 26 1480 142 28,5 1700 163 32,5 83,5
V785 6”

R½”

1140 107 17 1400 134 21 1620 152 25 1800 170 27 1970 190 30 2280 216 34 83,5

 

SECOND AIR JACKET OPEN

Burner NO Fittings Air Pressure
350 mms
Air Pressure
 500 mms
Air Pressure
700 mms
Air Pressure
900 mms
Air Pressure 1050 mms Air Pressure 1400 mms
Air Fuel Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h Air
m³/h
max
Fuel lt/h
max min max min max min max min max min max min
V780 1½”

R¼”

75 10,7 2,65 92 14 3,4 105 17,5 4,7 117 20,5 5,5 129 23,5 6,5 148 28 7,6
V781 2”

R¼”

144 22 4,5 177 27,3 5,5 204 33 6,8 230 40 8,3 250 45 9,5 289 56 12,2
V782 2”

R¼”

240 34 7,2 293 45 9,1 340 55 11,5 380 67 14,5 415 76 16,7 474 92 19,7
V783 6” R½” 432 63 13,7 528 82 18,2 612 100 22 680 118 25,8 750 137 29,5 864 167 36,5
V784 6”

R½”

850 124 24,3 104 159 32,1 1206 197 43 1340 233 47 1480 270 53,8 1700 325 66
V785 6”

R½”

1140 160 25,8 1400 211 33,3 1620 259 45 1800 310 48 1970 360 58 2280 432 68

 

Burner Gabarite Sizes

TYPE A B C D E

V 780

R1½" R¼" 142 170 330

V 781 - V 782

2" R¼" 178 218 370

V 783 - V 784 - V 785

6" R¼" 284 340 600

 

AnasayfaİletişimSite Ağacı